基于正序阻抗角的海上DFIG定子绕组匝间短路故障辨识
Inter-turn Short-circuit Fault Identification of Stator Winding for Offshore DFIG Based on Positive Sequence Impedance Angle
DOI:10.7500/AEPS20180425007
关键词: 双馈感应发电机  序分量模型  定子匝间短路  正序阻抗角  故障辨识
KeyWords: doubly-fed induction generator  sequence component model  stator inter-turn short-circuit  positive sequence impedance angle  fault identification
上网日期:2019-05-08
基金项目:国家重点研发计划资助项目(2017YFB0902800);上海市科技创新行动计划资助项目(18DZ1202400)
作者单位E-mail
魏书荣 上海电力大学电气工程学院, 上海市200090  
吴锐 上海电力大学电气工程学院, 上海市200090  
符杨 上海电力大学电气工程学院, 上海市200090 mfudong@126.com 
王健 国网上海市电力公司青浦供电公司, 上海市 201700  
周彬 上海绿色环保能源有限公司, 上海市 200433  
任浩翰 上海绿色环保能源有限公司, 上海市 200433  
摘要:
      为了保证海上双馈风力发电系统的安全可靠运行,提高海上DFIG定子绕组匝间短路故障辨识的精准度,文中提出一种以定子侧正序阻抗角为故障特征量的定子绕组匝间短路故障辨识方法。由于故障后各序分量不再对称,首先基于DFIG定子匝间短路故障状态下的序分量模型,推导得出DFIG定子侧正序阻抗角的表达式;然后分析电网电压不平衡、负载和转差率变化等非理想工况对该故障特征的影响规律,提出合理的故障辨识阈值。仿真与实验结果表明,该故障特征对电网电压不平衡具有鲁棒性,且通过合理设置故障阈值可实现对海上DFIG定子绕组匝间短路故障的精确辨识。
Abstract:
      In order to ensure the safe and reliable operation of offshore doubly-fed wind power generation system and improve the accuracy of inter-turn short-circuit fault identification of offshore doubly-fed induction generator(DFIG)stator winding, a stator inter-turn short-circuit fault identification method based on positive sequence impedance angle on stator side is proposed. Since the sequence components are no longer symmetrical after fault, the expression of positive sequence impedance angle of DFIG stator side is derived based on the sequence component model of DFIG stator inter-turn short-circuit fault. Then the influence of nonideal conditions such as unbalanced voltage, load and slip rate on the fault characteristics is analyzed, and a reasonable fault identification threshold is proposed. The simulation and experimental results show that the fault feature is robust to the unbalanced voltage of power grid, and the accurate identification of DFIG stator winding inter-turn short-circuit fault can be achieved by setting the fault threshold reasonably.