陈俊,李华忠,徐青山,等.基于断口两侧电压相量差的发电机机端断路器非全相保护[J].电力系统自动化,2018,42(21):125-130. DOI: 10.7500/AEPS20180116002.
CHEN Jun,LI Huazhong,XU Qingshan, et al.Open-phase Protection of Generator Circuit Breaker Based on Voltage Phasor Differences Between Two Sides of Breaking Point[J].Automation of Electric Power Systems,2018,42(21):125-130. DOI: 10.7500/AEPS20180116002.
基于断口两侧电压相量差的发电机机端断路器非全相保护
Open-phase Protection of Generator Circuit Breaker Based on Voltage Phasor Differences Between Two Sides of Breaking Point
DOI:10.7500/AEPS20180116002
关键词: 发电机  机端断路器  非全相保护  电压相量差  动模实验
KeyWords: generator  generator circuit breaker(GCB)  open-phase protection  voltage phasor difference  dynamic experiment
上网日期:2018-10-22
基金项目:
作者单位E-mail
陈俊 东南大学电气工程学院, 江苏省南京市 210096
南京南瑞继保电气有限公司, 江苏省南京市 211102 
chenj@nrec.com 
李华忠 南京南瑞继保电气有限公司, 江苏省南京市 211102  
徐青山 东南大学电气工程学院, 江苏省南京市 210096  
桂林 清华大学电机工程与应用电子技术系, 北京市 100084  
王光 南京南瑞继保电气有限公司, 江苏省南京市 211102  
钟守平 南京南瑞继保电气有限公司, 江苏省南京市 211102  
摘要:
      抽水蓄能机组和燃气轮机组的机端断路器(GCB)分合操作频繁,易发生非全相故障,且并网初期和解列时尚无保护功能可快速检测出该问题。文中采用对称分量法分析单机无穷大系统非全相故障时的断口两侧电压量特征,提出了基于断口两侧电压相量差的GCB非全相保护新原理,并通过动模实验加以验证。该原理不依赖电流量大小和断路器三相不一致接点,且不受电压互感器断线影响,可快速检测机组并网初期和解列时的GCB非全相故障。该原理已在广州抽水蓄能电站4台300 MW机组上投入使用,运行情况良好。
Abstract:
      The open-phase faults of pumped storage units and gas-turbine units may easily occur due to the frequent open and close operations of generator circuit breaker(GCB). It cannot be detected by the conventional protection during the initial period of grid-connection and in the normal operation of grid-disconnection. This paper adopts the symmetrical component method to analyze the voltage characteristics of both sides of the breaking point in the open-phase fault of a single-machine infinite system. Furthermore, this paper proposes a new principle of open-phase protection based on the voltage phasor differences between two sides of the breaking point. And the dynamic experiment is carried out to verify the correctness of the new criterion. Independent of current values and three-phase discrepancy contact status of the breaker, the new protection principle can quickly detect the open-phase fault during the initial period of grid-connection and in the normal operation of grid-disconnection for generating units, and it will not be affected by the potential transformer(PT)circuit failure. The principle has been used on four 300 MW pumped storage units of Guangzhou, China, and the operation is good.