文章摘要
崔晓丹,张红丽,方勇杰,等.暂态功角弱稳定模式辨识及其协调紧急控制策略[J].电力系统自动化,2018,42(1):91-97. DOI: 10.7500/AEPS20170512004.
CUI Xiaodan,ZHANG Hongli,FANG Yongjie, et al.Weak Stability Mode Identification of Transient Power Angle and Its Emergency Control Strategy[J].Automation of Electric Power Systems,2018,42(1):91-97. DOI: 10.7500/AEPS20170512004.
暂态功角弱稳定模式辨识及其协调紧急控制策略
Weak Stability Mode Identification of Transient Power Angle and Its Emergency Control Strategy
DOI:10.7500/AEPS20170512004
关键词: 暂态功角稳定  稳定模式  紧急控制  稳定裕度  负效应
KeyWords: transient power angle stability  stability mode  emergency control  stability margin  negative effect
上网日期:2017-11-30
基金项目:国家重点研发计划资助项目(2017YFB0902000);国家电网公司科技项目“基于安全域的电网安全稳定评估及辅助决策技术研究”
作者单位E-mail
崔晓丹 中国电力科学研究院有限公司, 北京市 100192; 南瑞集团有限公司(国网电力科学研究院有限公司), 江苏省南京市 211106; 智能电网保护和运行控制国家重点实验室, 江苏省南京市 211106  
张红丽 南瑞集团有限公司(国网电力科学研究院有限公司), 江苏省南京市 211106; 智能电网保护和运行控制国家重点实验室, 江苏省南京市 211106 zhanghongli@sgepri.sgcc.com.cn 
方勇杰 中国电力科学研究院有限公司, 北京市 100192; 南瑞集团有限公司(国网电力科学研究院有限公司), 江苏省南京市 211106; 智能电网保护和运行控制国家重点实验室, 江苏省南京市 211106  
李碧君 南瑞集团有限公司(国网电力科学研究院有限公司), 江苏省南京市 211106; 智能电网保护和运行控制国家重点实验室, 江苏省南京市 211106  
李威 南瑞集团有限公司(国网电力科学研究院有限公司), 江苏省南京市 211106; 智能电网保护和运行控制国家重点实验室, 江苏省南京市 211106  
牛拴保 国家电网公司西北分部, 陕西省西安市 710000  
摘要:
      针对电网发展过程中可能出现的复杂暂态功角失稳现象,提出了用于系统安全稳定分析和控制的暂态功角弱稳定模式的概念及其辨识方法,解析了紧急控制导致弱稳定模式演化为主导失稳模式的机理及其近似必要条件。在理论分析的基础上,提出了基于系统暂态稳定约束转化的紧急控制数学模型,进而设计了基于动态灵敏度指标的启发式协调紧急控制策略计算方法,提升了紧急控制算法对于处理复杂暂态失稳情况的适应性,实现了统筹系统暂态功角多个弱稳定模式的自动协调控制。基于实际电网的算例验证了所提紧急控制负效应机理及策略搜索算法的有效性。
Abstract:
      In concern of the instability of the complex transient power angle during the developing process of power grid, a concept of weak stability mode of transient power angle and its identification method are proposed to analyze and control the safety and stability of power system. The mechanism of weak stability mode evolving into dominant instability mode which is caused by the emergency control and its approximate necessary conditions are analyzed. Based on the theoretical analysis, a mathematical model of emergency control based on the transformation of system transient stability constraints is presented. Then a heuristic coordination emergency control strategy based on the dynamic sensitivity index is designed. The adaptability of emergency control algorithm to deal with the complex transient instability is improved and the automatic coordination control method to balance the multiple weak stability modes of power system transient power angle is realized. An example based on the actual grid is used to demonstrate the effectiveness of the presented mechanism of negative effects caused by the emergency control and the presented strategy search algorithm.
查看全文(Free!)   查看/发表评论  下载PDF阅读器