半月刊

ISSN 1000-1026

CN 32-1180/TP

+高级检索 English
多端柔性直流配电网高频功率相关性纵联保护方法
作者:
作者单位:

1.上海交通大学电子信息与电气工程学院,上海市 200240;2.国网浙江省电力有限公司余姚市供电公司,浙江省宁波市 315400

摘要:

直流线路保护是保障多端柔性直流配电网系统安全稳定运行的关键,主要技术难点在于故障区段的准确识别和快速隔离。文中分析了故障后直流配电网中暂态高频分量的分布特点,提出一种基于高频功率的直流线路纵联保护方法。利用故障前后高频功率的幅值变化,提出保护快速启动判据。利用不同故障情形下线路两侧高频功率线性关系和相关系数的差异,提出基于线路两侧高频功率相关系数的故障识别和选极判据。基于MATLAB/Simulink建立多端柔性直流配电网模型,仿真结果表明所提保护方法可快速、准确地判断故障线路和故障极,灵敏度与可靠性高,阈值易设定且相邻线路保护无须配合,对双端数据同步要求较低,不受系统运行方式影响和网络拓扑的限制,且具备良好的抗过渡电阻能力。

关键词:

基金项目:

国家自然科学基金青年基金资助项目(51807117);上海市教委科研创新重大项目(2019-01-07-00-02-E00044);上海市青年科技英才扬帆计划资助项目(17YF1410200)。

通信作者:

作者简介:

陈少宇(1995—),男,硕士研究生,主要研究方向:直流配电网继电保护。E-mail:chenshaoyu@sjtu.edu.cn
黄文焘(1988—),男,通信作者,副教授,博士生导师,主要研究方向:配电网、微电网和分布式新能源控制与保护。E-mail:hwt8989@sjtu.edu.cn
邰能灵(1972—),男,教授,博士生导师,主要研究方向:电力系统继电保护和电力系统综合自动化。E-mail:nltai@sjtu.edu.cn


Pilot Protection Method for Multi-terminal Flexible DC Distribution Network Based on Correlation of High-frequency Power
Author:
Affiliation:

1.School of Electronic Information and Electrical Engineering, Shanghai Jiao Tong University, Shanghai 200240, China;2.Yuyao Electric Power Supply Company of State Grid Zhejiang Electric Power Co., Ltd., Ningbo 315400, China

Abstract:

DC line protection is the key to ensure the safe and stable operation of the multi-terminal flexible DC distribution system. The main technical difficulties include the accurate identification and rapid isolation of the fault section. Distribution characteristics of the transient high-frequency components in DC distribution network after the fault are analyzed, and a pilot protection method for DC lines based on the transient high-frequency power is proposed. Based on the amplitude variation of the high-frequency power before and after the fault, the fast starting criterion for protection is proposed. According to the difference of linear relationship and correlation coefficient of high-frequency power on both sides of the line in different fault conditions, fault identification and pole selection criterion based on correlation coefficient of high-frequency power on both sides of the line is proposed. Based on MATLAB/Simulink, a multi-terminal flexible DC distribution network model is established. The simulation results show that the proposed protection method can quickly and accurately identify the fault line and fault pole with high sensitivity and reliability. Protection threshold is easy to be set and the protection coordination of adjacent lines is not required. Moreover, it has low requirements for data synchronization, and is not affected by system operation mode and network topology with good insusceptibility to fault resistance.

Keywords:

Foundation:
This work is supported by National Natural Science Foundation of China (No. 51807117), Major Scientific Research and Innovation Project of Shanghai Education Commission (No. 2019-01-07-00-02-E00044) and Shanghai Sailing Program (No. 17YF1410200).
引用本文
[1]陈少宇,黄文焘,邰能灵,等.多端柔性直流配电网高频功率相关性纵联保护方法[J].电力系统自动化,2020,44(19):150-159. DOI:10.7500/AEPS20200105002.
CHEN Shaoyu, HUANG Wentao, TAI Nengling, et al. Pilot Protection Method for Multi-terminal Flexible DC Distribution Network Based on Correlation of High-frequency Power[J]. Automation of Electric Power Systems, 2020, 44(19):150-159. DOI:10.7500/AEPS20200105002.
复制
分享
历史
  • 收稿日期:2020-01-05
  • 最后修改日期:2020-04-03
  • 录用日期:
  • 在线发布日期: 2020-10-15
  • 出版日期:
相关附件