半月刊

ISSN 1000-1026

CN 32-1180/TP

+高级检索 English
单相接地时高压直流换相电压相位偏移量特性
作者:
作者单位:

1.广东电科院能源技术有限责任公司,广东省广州市510080;2.直流输电技术国家重点实验室,南方电网科学研究院有限责任公司,广东省广州市510663;3.华南理工大学电力学院,广东省广州市510641

作者简介:

黄梦华(1994—),女,硕士研究生,主要研究方向:高压直流输电、电力系统稳定与控制。
傅闯(1973—),男,通信作者,博士,教授级高级工程师,主要研究方向:高压直流输电、电力系统稳定与控制。E-mail:15367985136@163.com
汪娟娟(1974—),女,博士,教授,主要研究方向:电力系统稳定与控制、高压直流输电。

通讯作者:

基金项目:

国家自然科学基金资助项目(51777079);国家自然科学基金委员会-国家电网公司智能电网联合基金项目(U1766213);南方电网公司重点实验室项目(SKLHVDC-2019-KF-19)。


Phase Offset Characteristics of Commutation Voltage for HVDC with Single-phase Grounding Fault
Author:
Affiliation:

1.Guangdong Electric Power Research Institute Energy Technology Co., Ltd., Guangzhou510080, China;2.State Key Laboratory of HVDC, Electric Power Research Institute of China Southern Power Grid, Guangzhou510663, China;3.School of Electric Power, South China University of Technology, Guangzhou510641, China

Fund Project:

This work is supported by National Natural Science Foundation of China (No. 51777079), National Natural Science Foundation of China-State Grid Corporation of China Joint Fund Project (No. U1766213) and State Key Laboratory Project of China Southern Power Grid (No. SKLHVDC-2019-KF-19).

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
    摘要:

    高压直流输电系统逆变侧不对称故障会造成换流阀换相电压相位发生偏移,进而引起换相失败的发生,严重影响了系统的稳定运行。为此,对不对称故障下的换相电压偏移量特性进行研究,基于电力系统暂态分析方法,对不对称故障下高压直流输电系统进行正负零序分解,推导出YNy0接线和YNd1接线换流变压器阀侧三相电压幅值、相位的计算公式,得到不对称故障下12脉动换流阀换相电压的最大偏移量,并对换流变网侧交流母线线电压幅值进行计算,通过MATLAB解析计算分析不同类型故障接地阻抗下,换流阀换相电压偏移量的变化特性。PSCAD/EMTDC电磁暂态仿真结果证明了文中所分析换相电压偏移量影响特性的正确性。

    Abstract:

    Asymmetrical faults on the inverter side of the high voltage direct current (HVDC) transmission system will lead to the phase offset of commutation voltage of converter valve, which will cause commutation failures and seriously affect the stable operation of the system. So it is necessary to study the phase offset characteristics of commutation voltage under asymmetric faults. Based on the transient analysis method of the power system, the positive-, negative- and zero-sequence decompositions of the HVDC transmission system under asymmetric faults are carried out, and the calculation formulas for the amplitude and phase of the three-phase voltage on the valve side of the converter transformers for YNy0 and YNd1 wiring are derived, and the maximum deviation of the commutation voltage of the 12-pulsation converter valve under an asymmetric fault is obtained. In addition, the amplitude of the AC bus voltage on the grid side of the converter is calculated, based on MATLAB simulation software, the characteristic variation of commutation voltage offset of converter valve with different types of ground fault impedance are analyzed. The PSCAD/EMTDC electromagnetic transient simulation results prove the correctness of the influence characteristics of commutation voltage offset analyzed in this paper.

    表 1 不同k值换相电压最大偏移量所在阀组Table 1 Valve group wiring with maximum offset of commutation voltage with different k values
    参考文献
    相似文献
    引证文献
引用本文

黄梦华,傅闯,汪娟娟,等.单相接地时高压直流换相电压相位偏移量特性[J].电力系统自动化,2020,44(12):162-168. DOI:10.7500/AEPS20191021009.
HUANG Menghua,FU Chuang,WANG Juanjuan,et al.Phase Offset Characteristics of Commutation Voltage for HVDC with Single-phase Grounding Fault[J].Automation of Electric Power Systems,2020,44(12):162-168. DOI:10.7500/AEPS20191021009.

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2019-10-21
  • 最后修改日期:2020-02-25
  • 录用日期:
  • 在线发布日期: 2020-06-18
  • 出版日期: