半月刊

ISSN 1000-1026

CN 32-1180/TP

+高级检索 English
基于矢量偏离度的风电场集电线路故障定位方法
作者:
作者单位:

1. 新能源电力系统国家重点实验室(华北电力大学), 河北省保定市 071003;2. 国网无锡供电公司, 江苏省无锡市 214000; 3. 国电电力河北新能源开发有限公司, 河北省张家口市 075000

作者简介:

通讯作者:

基金项目:

国家自然科学基金资助项目(51677072)


Fault Location Method of Wind Farm Collection Line Based on Vector Deviation Degree
Author:
Affiliation:

1. State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources(North China Electric Power University), Baoding 071003, China; 2. State Grid Wuxi Power Supply Company, Wuxi 214000, China;3. Guodian Power Hebei New Energy Development Co. Ltd., Zhangjiakou 075000, China

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
    摘要:

    为解决风电场集电线路因短路故障造成的弃风窝电问题,提出了基于矢量偏离度的风电场集电线路故障区间定位方法。该方法根据各终端测量装置的电气量信息,采用综合矢量误差和三相总不平衡度构建了风电场短路故障时的理论计算值与真实测量值的矢量偏离度目标函数。根据偏离度计算结果,判断真实故障时的故障信息与假想故障区间信息的差异程度,最小差异对应的假想故障区间即为真实的故障区间。PSCAD/EMTDC仿真验证了所提方法在不同故障位置、故障区间、过渡电阻情况下的可行性,能够满足风电场对其集电线路故障定位精度的要求。

    Abstract:

    In order to solve the problem of wind curtailment and poor power transmission ability caused by short-circuit faults in wind farm collection lines, a fault location method for wind farm collection lines based on vector deviation is proposed. According to the electrical information of each terminal measurement device, the objective function of vector deviation between the theoretical calculation value and the real measurement value is constructed by using total vector error(TVE)and total three-phase unbalance. According to the calculation results of deviation degree, the difference between the information of real fault and imaginary fault interval is judged. The imaginary fault interval corresponding to the minimum difference is the real fault interval. PSCAD/EMTDC simulation results show that the proposed method is feasible for different fault locations, different fault intervals and different transition resistances, and can meet the requirements of wind farm for the accuracy of collection line fault location.

    参考文献
    相似文献
    引证文献
引用本文

张科,孙立志,朱永利,等.基于矢量偏离度的风电场集电线路故障定位方法[J].电力系统自动化,2019,43(10):127-133. DOI:10.7500/AEPS20180417004.
ZHANG Ke, SUN Lizhi, ZHU Yongli,et al.Fault Location Method of Wind Farm Collection Line Based on Vector Deviation Degree[J].Automation of Electric Power Systems,2019,43(10):127-133. DOI:10.7500/AEPS20180417004.

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2018-04-17
  • 最后修改日期:2019-03-24
  • 录用日期:2018-09-09
  • 在线发布日期: 2019-02-26
  • 出版日期: